SVR® Lubricant Conditioning System

A complete recovery and maintenance solution for mineral-oil based turbine lubricants. SVR® targets and removes the dissolved varnish pre-cursors which are the cause of varnish. By removing these waste oxidation by-products, you restore the oils original solvency properties which forces any solid varnish deposits to be dissolved back into the oil where they are removed permanently.

*SVR® is a registered trademark of EPT CLEAN OIL.

 

Download Brochure

Dimensions

Height

58” (147 cm)

98” (249 cm) with crane

Length

48” (122 cm)

Spill retention pan standard size. Contact factory for custom pan sizing.

Width

26” (66 cm)

Weight

700 lbs (318 kg)

Dimensions are approximations taken from base model and will vary according to options chosen.
Connections

Inlet

1.5” FNPT with locking ball valve

Outlet

1” FNPT with locking ball valve

Max reservoir Size

SVR1200 + SVR1200X

8,000 gal (30,000 liter) reservoir

SVR2400

Max 16,000 gal (60,000 liter) reservoir

Element Configuration

Particulate filter

SVR1200: HP107L18-VTM710-C-V

SVR2400: HP107L18-VTM710V

SVR1200X: no particulate filter included

Main Filter

SVR1200: ICB600524-V x 2

SVR2400: ICB600524-V x 4

SVR1200X: ICB600524-V x 2

Seals

Fluorocarbon + silicone

Operating Temperature

Fluid Temperature

86°F to 176°F

(30°C to 80°C)

Ambient Temperature

-4°F to 104°F

(-20C to 40C)

Materials of Construction

Housing

Carbon steel with industrial coating

ASME U Code optional

Tray

Carbon steel with industrial coating

Fittings

Swagelok® stainless

electric Motor

TEFC, 56-145 frame

1-1.5 hp, 1150-1750 RPM

Motor Starter

MSP (motor starter/protector) in an IP65, aluminum enclosure with short circuit and overload protection.

pump

Cast iron, positive displacement gear pump with internal relief. Maximum pressure on pump inlet 15 psi (1 bar). Consult factory for higher pressures.

pump bypass

Full bypass at 90 psi (6.2 bar)

total system flow

SVR1200

7-11 gpm

SVR2400

14-16 gpm

Controlled via flow control valve + flow meter (included standard).
ICB® Canister Flow Rates

SVR1200 + SVR1200X

5 gpm (18.9 lpm) max

SVR2400

10 gpm (37.9 lpm) max

Maximum system flow dependent on and will vary with motor selection.
Pneumatic Option Air Consumption

~40 cfm @ 80 psi

Air consumption values are estimated maximums and will vary with regulator setting.
Media Description

VTM

β3[C] 4000 particulate, insoluble oxidation by-product and water removal media

ICB®

ICB® Ion-Exchange resin media for molecular removal of acids, varnish deposits, soluble oxidation by-products and dissolved metal ions from mineral based turbine oil.

Fluid Compatibility

Petroleum and mineral based fluids only (standard). For phosphate ester and other specified synthetic fluids, see FSA (page 108) or contact factory.

Hazardous Environment Options

Select pneumatic powered unit (Power Option 00) or explosion proof NEC Article 501, Class 1, Division 1, Group C+D. Call for IEC, Atex or other requirements.